# EtherNet/IP

> Using EtherNet/IP for Allen-Bradley PLC tag communication

<Info>The Nominal Instrumentation Library is in alpha testing. To request access, open the [Support Portal](https://portal.usepylon.com/nominal).</Info>

# EtherNet/IP

EtherNet/IP config files declare an Allen-Bradley PLC endpoint, an optional local backplane route, and the scalar tags Nominal reads or writes. `EtherNetIPDevice` exposes those tags by local alias from Python and can publish boolean and numeric tag values to Nominal Core or Nominal Connect.

<Info>
  The EtherNet/IP client lives under `instro.ethernetip` and is provided by the `instro-ethernetip` package (a native backend). Install it with the `instro[ethernetip]` extra; it is also included in `instro[all]`.
</Info>

## Install

Install with the EtherNet/IP extra:

```bash theme={null}
uv add "instro[ethernetip]"
```

or with pip:

```bash theme={null}
pip install "instro[ethernetip]"
```

The standalone package also installs directly: `pip install instro-ethernetip`.

<Note>
  EtherNet/IP graduated out of the experimental `instro-unstable` package. If you used a pre-release
  build, update imports from `instro.unstable.ethernetip` to `instro.ethernetip` (and the native
  module from `instro.unstable._ethernetip` to `instro.ethernetip._ethernetip`), and install
  `instro[ethernetip]` instead of `instro-unstable[ethernetip]`.
</Note>

## Quickstart

This example opens a CompactLogix connection, polls scalar tags, and publishes numeric samples to Nominal Core.

<Tabs>
  <Tab title="Code">
    ```python theme={null}
    import time

    from instro.lib.publishers import NominalCorePublisher
    from instro.ethernetip import EtherNetIPDevice

    RID = "<dataset_rid>"  # Nominal Core dataset RID.

    # autostart opens the session and starts polling.
    with EtherNetIPDevice(config="compactlogix.json", autostart=True) as plc:
        # Publish boolean and numeric tag samples to Nominal Core.
        plc.add_publisher(NominalCorePublisher(dataset_rid=RID))

        # Let the background daemon collect one polling window.
        time.sleep(10)
    ```
  </Tab>

  <Tab title="Config (compactlogix.json)">
    Create `compactlogix.json` with the PLC connection and tag definitions:

    ```json theme={null}
    {
      "version": 1,
      "protocol": "ethernetip",
      "device": {
        "name": "line_plc",
        "description": "CompactLogix PLC for line telemetry",
        "manufacturer": "Allen-Bradley",
        "model": "CompactLogix 5332E 1769-L32E"
      },
      "connection": {
        "host": "192.168.1.10",
        "port": 44818,
        "route_path": {
          "hops": [
            {"type": "backplane", "slot": 0}
          ]
        }
      },
      "timing": {
        "poll_interval": 1.0
      },
      "tags": [
        {
          "alias": "motor_running",
          "tag_name": "MotorRunning",
          "data_type": "bool",
          "poll": true
        },
        {
          "alias": "line_speed",
          "tag_name": "LineSpeed",
          "data_type": "real",
          "poll": true
        }
      ]
    }
    ```
  </Tab>
</Tabs>

## Current support

EtherNet/IP support is intentionally narrow. It targets PLC tags whose names and scalar data types are known before runtime.

| Area                                         | Supported today                                                                             |
| -------------------------------------------- | ------------------------------------------------------------------------------------------- |
| PLC family                                   | Tested on Allen-Bradley CompactLogix 5332E 1769-L32E                                        |
| Transport                                    | EtherNet/IP explicit messaging over TCP                                                     |
| Route paths                                  | Direct connection, or local backplane slot hops only                                        |
| Background polling                           | Automatic batched reads for tags marked `poll: true` in the config                          |
| Streaming to Nominal Core or Nominal Connect | Boolean and numeric scalar tag values                                                       |
| Manual tag operations                        | Single-tag and batched non-string scalar reads, plus writes, through the native session API |
| Unsigned integer validation                  | `usint`, `uint`, `udint`, and `ulint` are implemented, but not validated                    |
| Tag discovery                                | Not supported                                                                               |
| UDTs                                         | Not supported                                                                               |
| Arrays                                       | Not supported                                                                               |

<Note>
  Other Allen-Bradley Logix-family PLCs may work through the same underlying protocol. Current hardware testing covers only CompactLogix 5332E 1769-L32E.
</Note>

## When to use each feature

A connection, scalar tag definitions, and `autostart=True` cover the common path. Use the fields and APIs below for specific EtherNet/IP requirements.

| Requirement                                                    | Use                                                   |
| -------------------------------------------------------------- | ----------------------------------------------------- |
| Stream live scalar PLC data to Nominal Core or Nominal Connect | `timing.poll_interval` + tags with `poll: true`       |
| Poll configured tags automatically                             | `timing.poll_interval` + tags with `poll: true`       |
| Reject out-of-range setpoints before PLC writes                | `write_min` / `write_max` on numeric tags             |
| Reach a PLC CPU behind a local chassis/backplane               | `connection.route_path.hops` with `type: "backplane"` |
| Read several PLC tags in one native request                    | `EtherNetIpSession.read_tags([...])`                  |

## Key concepts

### Lifecycle

The EtherNet/IP workflow has six steps:

1. Define PLC tags in a JSON config file or an `EtherNetIPConfig`.
2. Instantiate `EtherNetIPDevice(config)` with an optional connection override.
3. Call `open()` to establish the native EtherNet/IP session.
4. Call `start()` to begin background polling when timing is configured.
5. Read or write tags by alias with type validation.
6. Call `close()` to close the session and stop background polling.

Prefer a `with` statement for normal scripts so `close()` runs when the block exits. `close()` stops the background polling daemon, closes publishers, and closes the native EtherNet/IP session.

<Tip>
  Pass `autostart=True` to combine steps 3 and 4 by starting a background polling thread ([Background polling](#background-polling)). A `timing` section in the config must be provided when using `autostart=True`.
</Tip>

Opening the session and validating the config do not probe the PLC tag map. Tag existence and actual PLC type are only validated when PLC I/O touches the tag: either when the background polling task reads `poll: true` tags, or when the user explicitly calls `read_tag()`, `read_tags()`, or `write_tag()`.

Example `timing` section:

```json theme={null}
{
  "timing": {
    "poll_interval": 1.0
  }
}
```

### Supported data types

The config-driven API supports scalar PLC tag types. The `data_type` field is required for every tag so reads can validate that the PLC returned the expected kind before publishing. If the PLC returns a different kind than the configured `data_type`, `EtherNetIPDevice.read_tag()` raises `TypeError`.

| Data type | Python payload                            | Streaming to Nominal Core or Nominal Connect | Notes                                                                                     |
| --------- | ----------------------------------------- | -------------------------------------------- | ----------------------------------------------------------------------------------------- |
| `bool`    | `bool` read as `0` or `1` in measurements | Yes                                          | Boolean reads are published as numeric samples.                                           |
| `sint`    | `int`                                     | Yes                                          | 8-bit signed integer.                                                                     |
| `int`     | `int`                                     | Yes                                          | 16-bit signed integer.                                                                    |
| `dint`    | `int`                                     | Yes                                          | 32-bit signed integer.                                                                    |
| `lint`    | `int`                                     | Yes                                          | 64-bit signed integer.                                                                    |
| `usint`   | `int`                                     | Yes                                          | 8-bit unsigned integer. Implemented, but not validated.                                   |
| `uint`    | `int`                                     | Yes                                          | 16-bit unsigned integer. Implemented, but not validated.                                  |
| `udint`   | `int`                                     | Yes                                          | 32-bit unsigned integer. Implemented, but not validated.                                  |
| `ulint`   | `int`                                     | Yes                                          | 64-bit unsigned integer. Implemented, but not validated.                                  |
| `real`    | `float`                                   | Yes                                          | 32-bit floating point.                                                                    |
| `lreal`   | `float`                                   | Yes                                          | 64-bit floating point.                                                                    |
| `string`  | N/A                                       | No                                           | Allen-Bradley Logix `STRING` tags (`LEN` as `DINT`, `DATA` as `SINT[]`) are not supported |

<Warning>
  The config-driven EtherNet/IP API supports scalar tags only. Structured values cannot be declared as a tag `data_type`; if a configured scalar tag actually returns a structured value, it is treated as an expected-versus-actual PLC kind mismatch. `EtherNetIPDevice.read_tag()` raises `TypeError`.
</Warning>

### Strings

Allen-Bradley Logix `STRING` tags are encoded as `LEN` (`DINT`) plus `DATA` (`SINT[]`), which is unsupported at this time. Furthermore, string measurements are not supported by Nominal Core or Nominal Connect.

### Batched reads

Use the private native session to read several PLC tags in one request:

```python theme={null}
from instro.ethernetip._ethernetip import EtherNetIpBatchError, EtherNetIpSession

with EtherNetIpSession("192.168.1.10:44818", route_path_slots=[0]) as session:
    for name, result in session.read_tags(["MotorRunning", "LineSpeed"]):
        if isinstance(result, EtherNetIpBatchError):
            print(f"{name} failed: {result}")
            continue

        print(name, result.kind, result.value)
```

`read_tags()` preserves input order. The call raises `EtherNetIpError` only when the whole batch cannot be dispatched or parsed. Individual tag failures are returned in the result list as typed `EtherNetIpBatchError` instances such as `TagNotFoundError`, `DataTypeMismatchError`, or `CipError`, so successful tags in the same batch remain available.

### Background polling

With `timing` configured and polling started, `EtherNetIPDevice` reads every tag with `poll: true` in one batched native request at the configured interval.

If one tag in the batch fails, that tag is skipped for the current measurement and the other successful tag values are still published.

Poll only streamable scalar tags:

* `bool`
* signed and unsigned integer types
* `real`
* `lreal`

String tags, UDTs, and arrays are not part of the Python EtherNet/IP polling surface.

### Route paths

Route paths are limited to local backplane slot hops:

```json theme={null}
{
  "connection": {
    "host": "192.168.1.10",
    "port": 44818,
    "route_path": {
      "hops": [
        {"type": "backplane", "slot": 0}
      ]
    }
  }
}
```

The config schema allows multiple local backplane hops:

```json theme={null}
{
  "route_path": {
    "hops": [
      {"type": "backplane", "slot": 2},
      {"type": "backplane", "slot": 0}
    ]
  }
}
```

Current testing has covered one backplane hop.

<Warning>
  Network hops are not supported. A route path cannot hop through Ethernet to another PLC, remote chassis, or IP address. The only accepted hop type is `backplane`, and CIP port 1 is implied by the `slot` value.
</Warning>

### Tag discovery

Tag discovery is not supported. Every tag must be declared explicitly in the `tags` array with:

* a local `alias`
* the PLC `tag_name`
* the expected scalar `data_type`
* optional `poll`, `write_min`, and `write_max`

If the PLC tag's actual type differs from the configured `data_type`, an `EtherNetIPDevice.read_tag()` call raises `TypeError`.

### Write limits

Set `write_min` and `write_max` to reject unsafe writes before they reach the PLC:

```json theme={null}
{
  "alias": "speed_setpoint",
  "tag_name": "SpeedSetpoint",
  "data_type": "real",
  "write_min": 0.0,
  "write_max": 2500.0
}
```

```python theme={null}
plc.write_tag("speed_setpoint", 1200.0)  # OK
plc.write_tag("speed_setpoint", 9999.0)  # Raises ValueError
```

EtherNet/IP checks write limits against the value passed by the caller before sending the write to the PLC.

## Configuration

Every EtherNet/IP config file must include:

* **`version`**: identifies the config schema version.
* **`protocol`**: must be `"ethernetip"` so the wrong protocol config fails clearly.
* **`device`**: metadata used for channel naming.
* **`tags`**: explicit tag definitions.

### Full configuration example

```json theme={null}
{
  "version": 1,
  "protocol": "ethernetip",
  "device": {
    "name": "line_plc",
    "description": "CompactLogix PLC for line telemetry",
    "manufacturer": "Allen-Bradley",
    "model": "CompactLogix 5332E 1769-L32E"
  },
  "connection": {
    "host": "192.168.1.10",
    "port": 44818,
    "route_path": {
      "hops": [
        {"type": "backplane", "slot": 0}
      ]
    }
  },
  "timing": {
    "poll_interval": 1.0
  },
  "tags": [
    {
      "alias": "motor_running",
      "tag_name": "MotorRunning",
      "data_type": "bool",
      "description": "Motor run feedback",
      "poll": true
    },
    {
      "alias": "line_speed",
      "tag_name": "LineSpeed",
      "data_type": "real",
      "description": "Measured line speed in rpm",
      "poll": true
    },
    {
      "alias": "part_count",
      "tag_name": "PartCount",
      "data_type": "dint",
      "description": "Completed parts since reset",
      "poll": true
    },
    {
      "alias": "speed_setpoint",
      "tag_name": "SpeedSetpoint",
      "data_type": "real",
      "description": "Commanded line speed in rpm",
      "poll": false,
      "write_min": 0.0,
      "write_max": 2500.0
    }
  ]
}
```

### Device section

The `device` section describes the physical PLC. `EtherNetIPDevice` uses the `name` field as a prefix for published channel names.

| Field          | Required | Description                              |
| -------------- | -------- | ---------------------------------------- |
| `name`         | Yes      | Device name, used as channel name prefix |
| `description`  | No       | Human-readable description               |
| `manufacturer` | No       | Device manufacturer                      |
| `model`        | No       | Device model number                      |

### Connection section

| Field        | Required | Default | Description                         |
| ------------ | -------- | ------- | ----------------------------------- |
| `host`       | Yes      | -       | PLC IP address or hostname          |
| `port`       | No       | `44818` | EtherNet/IP TCP port                |
| `route_path` | No       | -       | Optional local backplane route path |

#### Route path

| Field  | Required | Default | Description                          |
| ------ | -------- | ------- | ------------------------------------ |
| `hops` | No       | `[]`    | Ordered list of local backplane hops |

Each hop must be:

| Field  | Required | Description                  |
| ------ | -------- | ---------------------------- |
| `type` | Yes      | Must be `"backplane"`        |
| `slot` | Yes      | Backplane slot number, 0-255 |

### Tag definitions

Each tag entry defines one aliasable PLC tag:

| Field         | Required | Default | Description                                               |
| ------------- | -------- | ------- | --------------------------------------------------------- |
| `alias`       | Yes      | -       | Unique local alias used in `read_tag()` and `write_tag()` |
| `tag_name`    | Yes      | -       | PLC tag name                                              |
| `data_type`   | Yes      | -       | Expected scalar PLC data type                             |
| `description` | No       | -       | Optional human-readable description                       |
| `poll`        | No       | `true`  | Include this tag in background polling                    |
| `write_min`   | No       | -       | Minimum allowed write value for numeric tags              |
| `write_max`   | No       | -       | Maximum allowed write value for numeric tags              |

### Timing section

| Field           | Required | Default | Description                             |
| --------------- | -------- | ------- | --------------------------------------- |
| `poll_interval` | Yes      | -       | Polling interval in seconds (0.01-10.0) |

When the `timing` section is present, `EtherNetIPDevice` reads tags with `poll: true` in a batched background request at the specified interval. Successful values are published and buffered for retrieval.

### Validation rules

`EtherNetIPDevice` validates configuration at load time:

* `protocol` must be `"ethernetip"`.
* Tag aliases must be unique.
* Every tag must declare `data_type`.
* `data_type` must be one of the [supported scalar types](#supported-data-types).
* Only numeric tags can use `write_min` and `write_max`.
* `write_min` must be less than or equal to `write_max`.
* Integer write limits must fit in the configured PLC integer type.
* Route path hops must be local backplane hops with slots from 0 to 255.

Load-time validation is local to the config. It does not verify that PLC tags exist or that their actual PLC types match `data_type`; those checks happen only when the background polling task runs or when the user explicitly initiates a `read_tag()`, `read_tags()`, or `write_tag()` operation.

## Create an EtherNetIPDevice instance

<Tabs>
  <Tab title="JSON config">
    ```python theme={null}
    from instro.ethernetip import EtherNetIPDevice

    # Uses the connection section from compactlogix.json.
    with EtherNetIPDevice(config="compactlogix.json") as plc:
        # Assumes "line_speed" is a specified tag in compactlogix.json
        # and that 1200.0 is a valid value.
        measurement = plc.read_tag("line_speed")
        plc.write_tag("line_speed", 1200.0)
    ```
  </Tab>

  <Tab title="Connection override">
    ```python theme={null}
    from instro.ethernetip import EtherNetIPDevice

    with EtherNetIPDevice(
        config="compactlogix.json",
        # Overrides any connection in the config; the config can omit connection.
        connection={
            "host": "192.168.1.10",
            "port": 44818,
            # Local backplane hop to the PLC CPU slot.
            "route_path": {"hops": [{"type": "backplane", "slot": 0}]},
        },
    ) as plc:
        measurement = plc.read_tag("line_speed")
    ```
  </Tab>

  <Tab title="Python config">
    ```python theme={null}
    from instro.lib.types import DeviceInfo
    from instro.ethernetip import (
        EtherNetIPConfig,
        EtherNetIPConnectionInfo,
        EtherNetIPDevice,
        TagDef,
        TimingConfig,
    )

    config = EtherNetIPConfig(
        device=DeviceInfo(name="line_plc"),
        # Required when autostart should begin background polling.
        timing=TimingConfig(poll_interval=1.0),
        tags=[
            TagDef(alias="ready", tag_name="Ready", data_type="bool"),
            TagDef(alias="line_speed", tag_name="LineSpeed", data_type="real"),
        ],
    )

    # Keep environment-specific connection details separate from the tag map.
    connection = EtherNetIPConnectionInfo(
        host="192.168.1.10",
        # Local backplane hop to the PLC CPU slot.
        route_path={"hops": [{"type": "backplane", "slot": 0}]},
    )

    # Opens the session and starts polling immediately because timing is configured.
    with EtherNetIPDevice(config, connection=connection, autostart=True) as plc:
        measurement = plc.read_tag("line_speed")
    ```
  </Tab>
</Tabs>

## Read and write

Returned `Measurement` and `Command` objects use channel names in the pattern `{device_name}.{tag_alias}`. Write commands append `.cmd` to the channel name.

```python theme={null}
# The config examples above name the device "line_plc".
measurement = plc.read_tag("line_speed")
print(measurement.channel_data["line_plc.line_speed"])

command = plc.write_tag("line_speed", 1200.0)
print(command.channel_data["line_plc.line_speed.cmd"])
```

## Background polling

Use `autostart=True` to open the session and begin background polling immediately:

```python theme={null}
from instro.lib.publishers import NominalCorePublisher
from instro.ethernetip import EtherNetIPDevice

plc = EtherNetIPDevice(config="compactlogix.json", autostart=True)
plc.add_publisher(NominalCorePublisher(dataset_rid="<dataset_rid>"))

recent_speed = plc.get_channel("line_plc.line_speed", length=100)
plc.close()
```

Start explicitly when the session should open before polling begins:

```python theme={null}
plc = EtherNetIPDevice(config="compactlogix.json")
plc.open()
plc.start()
```

## Error handling

EtherNet/IP raises these errors for common failures:

| Error                                                                               | Meaning                                                                                                                        |
| ----------------------------------------------------------------------------------- | ------------------------------------------------------------------------------------------------------------------------------ |
| `RuntimeError: EtherNet/IP support requires the native package 'instro-ethernetip'` | The native PyO3 package is not installed. Install `instro[ethernetip]`.                                                        |
| `RuntimeError: EtherNet/IP client not connected. Call open() first.`                | A read or write occurred before `open()`.                                                                                      |
| `TypeError: Tag '{alias}' expected PLC kind ...`                                    | The PLC returned a different kind than the configured scalar `data_type`, including a structured value for a scalar tag.       |
| `ValueError: Tag '{alias}' value ... is below write_min`                            | A write was rejected by local bounds checking.                                                                                 |
| `ValueError: Tag '{alias}' raw value ... is out of range for ...`                   | A raw integer write does not fit in the configured PLC integer type.                                                           |
| Native `EtherNetIpError`                                                            | The underlying EtherNet/IP request failed because of a connection, CIP, or tag error.                                          |
| Native `EtherNetIpBatchError`                                                       | One tag in a `read_tags()` batch failed. Check subclasses such as `TagNotFoundError`, `DataTypeMismatchError`, and `CipError`. |

## Known limitations

* EtherNet/IP support is installed through `instro[ethernetip]` (or the standalone `instro-ethernetip` package).
* Hardware testing covers Allen-Bradley CompactLogix 5332E 1769-L32E.
* Route paths support local backplane hops only. Network hops are unsupported.
* Current testing covers one local backplane hop.
* Tag discovery is unsupported.
* Arrays and UDTs are unsupported.
* PLC string tags are not exposed through the Python EtherNet/IP API.